ICM293 Spec Sheet
ICM293 Intermittent Pilot Gas Ignition Control
ICM293 Intermittent Pilot Gas Ignition Control
Intermittent Pilot Gas Ignition Control - replacement for popular models, including Lennox 30W33 and JCI G776RGD-14 series controls.
Specifications:
- Control Voltage: Line 24V (18-30 VAC), 50/60Hz
- Anticipator Setting: 0.2A plus valve load @ 24VAC
- Prepurge: 15 seconds
- Trial for Ignition: 85 seconds
- Lockout: 60 minutes
- Flame Failure Response Time: 0.5 seconds
- LED: See product label for error codes