Specifications:
  • Input, High Fire: 1,200 MBTU/h (352 kW)
  • Output, High Fire: 1,044 MBTU/h (306 kW)
  • Input, Low Fire: 600 MBTU/h (176 kW)
  • Output, Low Fire: 522 MBTU/h (153 kW)
  • Vent Size (Cat. IV): 6"
  • Combustion Air Size: 6"
  • Electrical: Controls: 120V / single phase / 20A
Standard Equipment:
  • Water flow switch
  • Low water cutoff with test light and manual reset button
  • Manual reset high limit
  • ASME CSD-1
  • Manual firing valve
  • Leak test valve
  • High gas pressure switch
  • Low gas pressure switch
  • Modulation capabilities down to 50% of full fire
  • ASME 160 lb. w.p. heat exchanger
  • Less than 10ppm NOx
  • Air pressure switch
  • Pump time delay
  • Low-fire start time delay
  • 75 psi pressure relief valve (RHCH)
  • 125 psi pressure relief valve (RhCV)
  • Temperature and pressure gauge
  • Indicator/status lights for: Power On, Call for Heat, Pre-Pruge, Burner On, Ignition failure
  • Pump time delay (adjustable 0.1 to 10 min.)
  • Selector switch for internal or external (0-10VDC) control
  • 87% Efficiency

RheosBoilerWH RHCHRHCV.pdf